APC Easy UPS 3S 20kVA 400V 3:3 UPS ( E3SUPS20KHB1)
APC Easy UPS 3S 20kVA 400V 3:3 UPS ( E3SUPS20KHB1) High-efficiency 3-phase UPS with internal batteries providing a runtime of 15 minutes. The UPS features advanced product features, competitive specifications,
Product specifications
acoustic level |
63 dBA
|
|
---|---|---|
battery curve |
B
|
|
battery type |
External battery system
|
|
bypass type |
Built-in maintenance bypass
|
|
product certifications |
CE EAC RCM WEEE
|
|
crest factor |
3 : 1
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0057
|
|
curve load maximum |
100 %
|
crest factor |
3: 1
|
|
---|---|---|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0057
|
|
curve load maximum |
100 %
|
|
curve load minimum |
1 %
|
|
curve proportional loss |
0.0209
|
|
curve square loss |
0.0256
|
|
curve test cond ID |
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) output.
|
|
curve X-axis maximum |
100 %
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
extended runtime |
0
|
|
maximum input current |
55 A
|
|
Maximum configurable power in VA |
30000 VA
|
|
Maximum configurable power in W |
30000 W
|
|
maximum short-circuit current |
10 kA
|
|
liquid value |
0
|
|
load power factor |
0.9 leading to 0.9 lagging
|
|
mounting mode |
Not rack-mountable
|
|
mounting preference |
No preference
|
|
number of battery filled slots |
0
|
|
number of battery free slots |
0
|
|
cos phi |
0.99
|
|
depth |
80 cm
|
|
height |
77 cm
|
|
Number of power module-filled slots |
0
|
|
Number of power module free slots |
0
|
|
net weight |
60 kg
|
|
rated power in VA |
30000 VA
|
|
rated power in W |
30000 W
|
|
width |
25 cm
|
|
operating altitude |
0…3281 ft
|
|
output overload operation |
10 minutes at 125% and 60 seconds at 150%
|
|
ambient air temperature for operation |
0
40 °C
|
|
ambient air temperature for storage |
-15
40 °C
|
|
storage altitude |
0.00
14999.82 m
|
|
standards |
IEC 62040-1-1 IEC 62040-2 IEC 62040-3 IEC 62040-4 ISTA 2B
|
|
UPS size |
WS
|
|
UPS type |
Double conversion online
|
|
graph display |
1
|
|
redundant |
No
|
|
show note OP temperature |
No
|
|
two post mountable |
0
|
|
No
|
||
colour |
White
|
|
input voltage limits |
304…477 V
|
|
input voltage |
400 V 3 phases
|
|
IP degree of protection |
IP20
|
|
network frequency |
45…65 Hz
|
|
output voltage |
400 V 3 phases
|
|
provided equipment |
Dust filter Installation guide
|
|
relative humidity |
0
95 % non-condensing
|
|
Battery power in VAH |
0 VAh runtime
|
|
inputvolt_other |
380 V 415 V
|
|
outputvolt_other |
380 V 415 V
|
|
harmonic distortion |
Less than 3 %
|
heat dissipation |
1410 Btu/h
|
---|
output frequency |
50 Hz sync to mains 60 Hz sync to mains
|
---|
Package 1 Weight |
77 kg
|
|
---|---|---|
Package 1 Height |
101.5 cm
|
|
Package 1 width |
40 cm
|
|
Package 1 Length |
98.2 cm
|
EU RoHS Directive |
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration
|
|
---|---|---|
Mercury free |
Yes
|
|
RoHS exemption information |
Yes
|
|
China RoHS Regulation |
China RoHS declaration Product out of China RoHS scope. Substance declaration for your information
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
|
Optimized Energy Efficiency |
Energy efficient product
|